Vertiv has expanded its 800 VDC power portfolio for AI data centers. The company announced from Dubai on 27 November 2026 that it is adding systems for the AI compute pod and the data hall. These sit alongside the rack-level Vertiv PowerDirect 5000 Power Rack, which launched in May 2026. Operators can now introduce 800 VDC at three levels: the rack, the pod or the whole hall.
Vertiv says AC and DC architectures will coexist for some time, and that operators are weighing 800 VDC as one route to higher-density computing rather than a single standard. The pitch is that customers can add DC at the point in the power train that suits them, without committing a whole facility to it.
800 VDC at the rack
The PowerDirect 5000 (±400 / 800 VDC) Power Rack sits next to the IT rack. It can be configured up to 800 kW and takes in facility 480 VAC. It outputs 800 VDC or ±400 VDC. It holds 30 hot-pluggable 30 kW power supply units and an integrated battery backup unit designed for at least 50 seconds of hold-up time.
Inside the compute rack, the PowerDirect 3000 90 kW 19-inch power shelf is a 1U DC-DC converter. It steps 800 VDC down to 54 VDC for the compute trays, with up to 98.5% peak efficiency and support for 180% pulse power for 0.5 milliseconds.
Vertiv positions this setup for brownfield sites and retrofits. Moving conversion and storage out of the IT rack frees 8 to 16 rack units for compute, and existing upstream AC infrastructure can stay in place.
800 VDC at the pod
The PowerDirect 9000 1.5 MW 800 VDC Power Center converts 480 VAC to 800 VDC for a full row or pod. Power travels over the PowerBar Track DC busway and tap-off boxes to a PowerDirect 3000 shelf in each rack. The system scales in 60 kW steps through 27 hot-pluggable power supply units.
The EnergyCore Li5 800 VDC battery cabinet connects straight to the DC bus. It provides 200 kW of continuous backup at up to 98% conversion efficiency, and up to six cabinets can run in parallel with active current sharing. Vertiv says the design suits colocation providers that host tenants with different workloads and GPU generations, because it supports mixed AC and DC loads.
800 VDC at the data hall
At the top end is the PowerNexus MV SST, a 5 MW solid-state transformer. It converts medium-voltage AC directly to 800 VDC in one stage and feeds the Vertiv DC busway. Vertiv says this removes two to three intermediate conversion steps found in conventional power trains. The unit is outdoor-rated, liquid-cooled and containerized, with up to 98% AC-to-DC efficiency and galvanic isolation.
With external energy storage and a DC/DC converter on the 800 VDC bus, it can provide fault ride-through and AI power smoothing. A single unit can support a 4.8 MW super pod reference architecture without chaining. Power can also flow in both directions, which Vertiv says improves grid power quality and can provide active power support. The company aims it at campus-scale AI factories.
Safety and services
Vertiv says its 800 VDC designs include touch-proof busbars, high-voltage isolation, midpoint grounding, ground-fault detection and arc-flash prevention. Vertiv Services offerings developed for DC environments support them.
“The 800 VDC power train is not just a new power product or conversion methodology; it is a set of architectures and system designs,” said Scott Armul, Chief Product and Technology Officer at Vertiv.
Where it stands
Pilot programs, technical validation and collaborative development work with customers are under way, according to Vertiv.