Vertiv has widened its 800 VDC power portfolio for AI data centers, adding systems for the compute pod and the data hall. Until now, the range was limited to the rack-level Vertiv PowerDirect 5000 Power Rack, introduced in May 2026. The US-listed infrastructure company (NYSE: VRT) announced the expansion from Dubai on 27 November 2026.
Vertiv’s pitch is that 800 VDC will not replace AC overnight. The company expects AC and DC architectures to coexist, so operators need to be able to bring in 800 VDC at different points in the power train rather than redesign a whole facility around it.
Rack level: PowerDirect 5000 and 3000
The PowerDirect 5000 sits next to the IT rack and can be configured up to 800 kW. It takes 480 VAC from the facility and outputs either 800 VDC or ±400 VDC. It holds 30 hot-pluggable 30 kW power supply units and an integrated battery backup unit that Vertiv says is designed for at least 50 seconds of hold-up time.
Inside the compute rack, the 1U PowerDirect 3000 90 kW power shelf steps 800 VDC down to 54 VDC for the compute trays. Vertiv quotes up to 98.5% peak efficiency and 180% pulse power for 0.5 milliseconds.
Moving conversion and storage out of the IT rack frees 8 to 16 rack units for compute, the company says. The design targets brownfield and retrofit sites, because existing upstream AC infrastructure can stay in place.
Pod level: PowerDirect 9000
The PowerDirect 9000 is a 1.5 MW power center that converts 480 VAC to 800 VDC for a whole row or pod. Power then travels over the PowerBar Track DC busway and tap-off boxes to a PowerDirect 3000 shelf in each rack. The system scales in 60 kW steps across 27 hot-pluggable power supply units.
Backup comes from the EnergyCore Li5 800 VDC battery cabinet, which connects straight to the DC bus. Each cabinet provides 200 kW of continuous backup at up to 98% conversion efficiency, and up to six can run in parallel with active current sharing. Vertiv positions the pod design for colocation providers hosting tenants with different workloads and GPU generations.
Data hall level: PowerNexus MV SST
At the top of the range is the PowerNexus MV SST, a 5 MW solid-state transformer. It converts medium-voltage AC directly to 800 VDC in one stage, removing two to three conversion steps found in conventional power trains. It is outdoor-rated, liquid-cooled and containerized, with up to 98% AC-to-DC efficiency and galvanic isolation.
Vertiv says it can provide fault ride-through and AI power smoothing when paired with external energy storage and a DC/DC converter on the 800 VDC bus. A single unit can support a 4.8 MW super pod reference architecture without chaining, and bidirectional power flow allows grid support. The target customer is a campus-scale, purpose-built AI factory.
Safety and next steps
Vertiv says the architectures include touch-proof busbars, high-voltage isolation, midpoint grounding, ground-fault detection and arc-flash prevention. They are backed by Vertiv Services offerings developed for DC environments.
“Every layer, from the medium-voltage grid to the compute tray, is designed to work together, with safety built for DC operation,” said Scott Armul, Chief Product and Technology Officer at Vertiv.
Pricing and availability
Vertiv has not published pricing or general availability dates. It says pilot programs, technical validation and collaborative development projects tailored to customer deployments are currently under way.