Vertiv has introduced the PowerNexus MV UPS, an outdoor-rated, medium-voltage power system built for AI data centers. The company announced it from Dubai on 25 November 2026. It targets colocation, neocloud and hyperscale operators who are stuck waiting for utility interconnection or running short of indoor space. Vertiv says it is already talking to customers worldwide, with shipments expected to start in mid-2027.
What the PowerNexus MV UPS does
The system sits outdoors at the point of connection to the grid. It combines a medium-voltage UPS, fault ride-through and AI power smoothing on one platform. Moving this equipment out of the data hall leaves more indoor floor space for servers and accelerators, which is where operators earn their revenue.
Vertiv lists the following capabilities:
- Class 1 output quality: when paired with long-duration battery systems, it delivers Class 1 output voltage under IEC 62040-3, to protect critical loads during grid disturbances and upstream faults.
- Fault ride-through and power smoothing: it is designed to support grid stability during faults and to absorb fast swings in AI workloads before they reach the grid.
- Efficiency: a line-interactive topology gives up to 98.5% efficiency at peak operation, according to the company.
- Less diesel: with long-duration batteries, it can run on battery power for up to four hours, which Vertiv says can reduce reliance on diesel generators for longer backup.
- Single-vendor skid: the UPS, batteries and other powertrain components come as one architecture, which should cut coordination work during deployment.
- Simulation model: a PSCAD model lets customers simulate behaviour and check power quality and dynamic interactions with the wider grid before installation.
“The Vertiv PowerNexus MV UPS is designed as a system-level response to those challenges,” said Kyle Keeper, senior vice president of the power management business unit at Vertiv, referring to grid queues, space limits and changing grid requirements.
Proof-of-concept testing
Vertiv recently ran proof-of-concept demonstrations with QTS, SoftBank and Rosendin at its R&D and customer experience centre in Bologna, Italy. Tests covered steady-state and dynamic conditions. The company reports stable performance across 0–100% loads, Class 1 voltage accuracy during rapid load changes, and ride-through of a 100% voltage sag lasting 150 milliseconds and a 25% overvoltage lasting five seconds.
Ryan Kuithe, senior vice president of facilities operations at QTS, said the system kept power stable through dynamic load changes and voltage disturbances during testing.
New medium-voltage lab planned
Vertiv also plans a dedicated Medium Voltage Laboratory at the Bologna site, due to become operational in 2027. It will cover research and development, full-voltage validation, customer demonstrations, service training and system-level testing. Architectures in scope include MV UPS, MV to 800 VDC and battery energy storage.
Giovanni Zanei, vice president of large power conversion at Vertiv, said the lab will help customers evaluate new architectures as they plan power systems for AI-scale facilities, including 800 VDC designs.
Pricing and availability
Pricing has not been disclosed. Vertiv expects shipments of the PowerNexus MV UPS to begin in mid-2027. Customers can already arrange demonstrations and system validation with the company.